Warehouse lighting should follow the logic of storage, movement and order fulfilment rather than simply the geometry of the building. Rack aisles, high-bay storage, picking stations, dispatch areas and loading docks create different requirements for illuminance, optical distribution and lighting controls.
A good design therefore starts with the racking layout, routes used by people and vehicles, working positions and storage heights. Only after these elements are defined should the number, position and optics of the luminaires be determined.
EN 12464-1:2021 distinguishes between different warehouse and logistics activities. As reference values, it specifies 100 lx for storage areas, 150 lx at floor level in rack storage, 200 lx for loading and unloading areas and 300 lx for packing and dispatch activities. The final design should still reflect the actual visual task rather than applying a table value without considering how the area is used.
Order picking, for example, requires workers to identify labels, codes, documents and similar products quickly. This can justify a higher lighting level than an area used primarily for long-term storage.
In a narrow aisle between high racks, a standard wide-beam luminaire can direct a significant proportion of its output towards the upper rack structure instead of the floor and stored goods. Aisle optics should therefore be selected according to aisle width and mounting height.
Vertical illumination is also important. Labels, barcodes and rack markings need to remain readable at different heights rather than only at floor level. This becomes particularly important in manually picked storage facilities.
Luminaire positions should be coordinated with the final racking layout. If the lighting is installed before aisle positions are confirmed, fixtures may later end up directly above the racks instead of illuminating the actual working corridors.
In high-bay warehouses, high lumen output alone does not guarantee an effective solution. The optical system must deliver the required light to the task area from the actual mounting height while maintaining suitable uniformity.
Photometric calculations allow designers to compare output levels, optics and luminaire spacing before equipment is ordered. This helps prevent both underlighting and the unnecessary installation of excessive numbers of fixtures.
Maintenance access should also be considered in high spaces. Replacing or servicing a luminaire may require lifting equipment and temporary closure of an aisle. Reliability and future service planning are therefore part of the initial design.
Picking areas are generally more visually demanding than long-term storage. Employees work with individual items, labels, scanners and order lists, often at a fast pace. Lighting should support rapid identification while limiting strong shadows and distracting reflections.
Packing and dispatch involve additional tasks such as checking goods, reading shipping documents, applying labels and preparing consignments. EN 12464-1:2021 specifies 300 lx for a number of these logistics activities.
Loading docks form the transition between internal warehouse operations and external transport. Pedestrians, forklifts, pallet trucks and delivery vehicles may all move through the same area.
Lighting should make the dock edge, loading surface and potential obstacles clearly visible. Particular attention may also be required inside trailers and containers, where the main warehouse lighting may not provide sufficient visibility.
Transitions between indoor and outdoor areas should avoid extreme brightness contrasts that make visual adaptation more difficult.
Rack aisles can remain unoccupied for significant periods, making them suitable for presence or motion-based lighting control.
The warehouse can be divided into logical control zones. Lighting increases when a person or vehicle approaches and can return to a predefined background level when the area is unoccupied. If racking or traffic routes change, the control zones should be capable of being reconfigured.
Sensor coverage needs to reflect the actual direction of travel. Light should activate before a forklift or employee enters a dark aisle rather than only after movement is detected immediately beneath a fixture.
Racking can significantly alter visibility and escape routes within a warehouse. Emergency lighting should therefore be coordinated with the final storage configuration rather than designed only from an empty architectural plan.
EN 1838:2024 defines current requirements for emergency escape lighting and open areas following failure of the normal lighting supply. Exit signs, changes of direction, exits and relevant fire-safety equipment must remain clearly identifiable.
Large logistics facilities are not always completed or commissioned as one single stage. The lighting system can be organised so that equipment delivery and installation follow the actual warehouse fit-out programme.
For example, goods receiving and dispatch areas may be completed first, followed by selected racking sectors and later by additional storage zones. For this approach to work, the overall photometric and electrical design should already be defined, together with luminaire numbering, optical distributions, product specifications and control architecture.
Phased delivery should not mean designing each phase independently without an overall concept. Doing so can result in different luminaire families, incompatible controls and unnecessarily complicated future maintenance.
Effective warehouse lighting starts with the route of the goods: receiving, storage, picking, packing and dispatch. When photometric design follows this logistics flow, each area can use appropriate optics, illuminance and controls instead of applying one lighting solution throughout the entire warehouse.
Polaris Lighting provides warehouse lighting design and solutions for rack aisles, high-bay storage, picking and loading areas, sensor control, emergency lighting and phased project delivery. Contact us if you need a warehouse lighting solution designed around your logistics processes and project stages.